如果在控制器启动过程中出现I/O模块故障,它可能停止I/O初始化。因此,控制器启动过程未能完成,使应用程序挂起。已经对控制器启动进行了更改,以防止出现这种情况不会发生。
48模块配置的系统加电
AADvance支持的zui大I/O模块数控制器是48。某些配置,特别是当大多数是数字输出模块,会导致系统不电源循环后正确启动。对控制器的更改已经进行了启动以防止这种情况发生。
处理器失去同步在双处理器配置中,在某些情况下两个处理器失去同步的条件,但是继续异步运行。尽管I/O仍然去了它的在故障保护模式下,任何绑定数据都可能不正确。对控制器进行了更改,以防止这种情况发生正在发生。
虚假软错误检测(SED)故障- TN30056-01(回答id: 564815)
每个高 级模块使用一个或多个FPGA来提供处理器和I/O之间的通信接口模块。ADvance中使用的FPGA的制造商发布了产品通知,表明该设备可以虚假地产生SED错误。FPGA制造商对控制器进行了建议的更改,以防止这种情况的发生。
在线更新后,处理器失去同步有可能对超过37个的大型系统进行在线更新安装的I/O模块可能会导致处理器丢失同步。对控制器的更改包括防止这种情况发生。
T9110 数字输出模块 PLC与工业控制计算机
I/O initialization Stop - TN30051-01(Answer id. 544046).
If an I/O module fails during controller startup, it may stop I/O initialization. As a result, the controller startup process fails to complete, causing the application to hang. Changes have been made to the controller boot to prevent this from happening.
48 Modules are configured to power on the system
AADvance supports a maximum of 48 I/O modules. Certain configurations, especially when most are digital output modules, can cause the system to start properly after no power cycle. Changes to the controller have been initiated to prevent this from happening.
Processor out of sync In dual-processor configurations, in some cases both processors lose the condition of synchronization but continue to run asynchronously. Although I/O still goes out of its way in fail-safe mode, any bound data may be incorrect. Changes were made to the controller to prevent this from happening.
False Soft Error Detection (SED) fault - TN30056-01(Answer id: 564815)
Each advanced module uses one or more FPgas to provide a communication interface module between the processor and I/O. The manufacturer of the FPGA used in ADvance issued a product notice indicating that the device could falsely produce a SED error. FPGA manufacturers have made recommended changes to the controller to prevent this from happening.
Loss of processor synchronization after online update Possible for more than 37 large systems online update Installed I/O modules may cause processor loss of synchronization. Changes to the controller include preventing this from happening.