140CRA31200C 适配器模块 是S908总线的I/O主机
本指南介绍140CRA31908适配器模块。使用该模块将S908架构现代化到M580系统。
量子或984 cpu驱动S908非以太网里约热内卢架构。当您在M580系统的X80插槽中安装140CRA31908模块时,您可以将S908架构连接到该X80插槽,并允许S908网络与M580网络通信。
注意:140CRA31908模块不兼容量子以太网I/O架构;该模块不能被量子140CRP31200通信模块扫描。
注意:本指南中包含的特定配置设置仅用于教学目的。特定配置所需的设置可能与本指南中提供的示例有所不同。
两个以太网端口允许通过EIO网络与M580 ePAC进行隐式I/O交换。(隐式I/O交换的zui大帧大小为1,400字节。)当您将140CRA31908模块连接到以太网主环时,您可以使用两个以太网端口。
单个EIO网络中zui多支持31个适配器。网络拓扑请参考《Modicon M580双机热备,常用架构系统规划指南》(参见《Modicon M580双机热备,常用架构系统规划指南》)。
S908总线I/O主控的识别
在单个140CRA31908模块的配置中,140CRA31908是S908总线的I/O主机。
在具有冗余140cr31908模块的配置中,140CRP93•00模块上的Com Act LED标识I/O主机。

140CRA31200C 适配器模块 是S908总线的I/O主机
This document describes the 140CRA31908 adapter module. Use this module to modernize the S908 architecture to the M580 system.
Quantum or 984 cpu drives the S908 non-Ethernet Rio architecture. When you install the 140CRA31908 module in the X80 slot of the M580 system, you can connect the S908 architecture to that X80 slot and allow the S908 network to communicate with the M580 network.
Note: The 140CRA31908 module is not compatible with the Quantum Ethernet I/O architecture; The module cannot be scanned by the quantum 140CRP31200 communication module.
Note: The specific configuration Settings included in this guide are for instructional purposes only. The Settings required for a particular configuration may differ from the examples provided in this guide.
Two Ethernet ports allow for implicit I/O exchange with the M580 ePAC over the EIO network. (The maximum frame size for an implicit I/O exchange is 1,400 bytes.) When you connect the 140CRA31908 module to the Ethernet master ring, you can use two Ethernet ports.
A maximum of 31 adapters are supported in a single EIO network. For details about the network topology, see the Modicon M580 Dual-System Hot Backup, Common Architecture System Planning Guide (see the Modicon M580 Dual-System Hot Backup, Common Architecture System Planning Guide).
Identification of the S908 bus I/O master
In the configuration of a single 140CRA31908 module, 140CRA31908 is the I/O host for the S908 bus.
In a configuration with a redundant 140cr31908 module, the Com Act LED on the 140CRP93•00 module identifies the I/O host.